Specification Sheet:
Click to download specifications
630 mmsq Plain copper. X-HF-110 Insulated,
V90HT Nitrile modified PVC sheathed single core.
0.6/1KV to AS5000.1 with a flexible conductor.
For Fixed Application.
Construction
Conductor: Plain Copper Conductor to AS1125 Fine Copper Stranding to Class 5 & 6
Max. D.C. resistance at 20C: 0.0287 ohms / km.
Insulation: X-HF-110 1100C to AS/NZS5000.1
Nom. Wall Thickness: 2.4 mm.
Sheath: Coloured Nitrile modified P.V.C. type V90HT to AS3808.
Nominal Diameter: 42.5 mm.
Nom. Wall Thickness: 2.2 mm.
Identification: Cable marked at intervals not exceeding 500mm – “LHDN630 630mmsq PAC AUSTECH W&C X-HF-110 0.6/1KV ELECTRIC CABLE”
Amp rating @ 30°C: 1154*
*Current-carrying capacity to AS/NZS 3008.1.1:2009 Table 9 Touching
Reference Standards:
AS1125 Max. conductor Resistance
AS3808 INSULATION and sheath compound type.
AS5000 Construction to 0.6/1KV sheathed single core for fixed applications CABLE TESTS TO TABLE 5 AS APPLICABLE
AS3008 Power Amp Ratings, Voltage Drop, Derating Factors.